Phasor measurement units (PMUs) are the measurement devices fostering the transformation of electric power networks towards the smart grid paradigm. They should accurately measure synchrophasors, frequency, and rate of change of frequency (ROCOF), so that the management and control applications relying on PMU-based distributed monitoring systems can operate effectively. Commercial PMUs performance is typically guaranteed by the compliance with the IEEE standard C37.118.1, which is focused on PMUs for power transmission systems and defines testing conditions and error limits. However, actual operating conditions are much more variable than those covered by the standard, especially when PMUs are used in distribution networks. In particular, the standard does not consider unbalance, which may be negligible neither in transmission nor in distribution grids. For the first time, this paper analyzes the impact of unbalance on the accuracy of four of the most significant classes of signal processing algorithms for PMU measurements. Synchrophasor, frequency, and ROCOF estimation performances under different unbalance conditions are investigated in the test cases suggested by the IEEE C37.242-2013 guide. Novel analytic expressions to predict the errors are derived and validated, and they are proved to be useful for an effective implementation of PMU algorithms intended for both distribution and transmission systems.

Effect of Unbalance on Positive-Sequence Synchrophasor, Frequency, and ROCOF Estimations

Castello, Paolo;Pegoraro, Paolo Attilio;
2018-01-01

Abstract

Phasor measurement units (PMUs) are the measurement devices fostering the transformation of electric power networks towards the smart grid paradigm. They should accurately measure synchrophasors, frequency, and rate of change of frequency (ROCOF), so that the management and control applications relying on PMU-based distributed monitoring systems can operate effectively. Commercial PMUs performance is typically guaranteed by the compliance with the IEEE standard C37.118.1, which is focused on PMUs for power transmission systems and defines testing conditions and error limits. However, actual operating conditions are much more variable than those covered by the standard, especially when PMUs are used in distribution networks. In particular, the standard does not consider unbalance, which may be negligible neither in transmission nor in distribution grids. For the first time, this paper analyzes the impact of unbalance on the accuracy of four of the most significant classes of signal processing algorithms for PMU measurements. Synchrophasor, frequency, and ROCOF estimation performances under different unbalance conditions are investigated in the test cases suggested by the IEEE C37.242-2013 guide. Novel analytic expressions to predict the errors are derived and validated, and they are proved to be useful for an effective implementation of PMU algorithms intended for both distribution and transmission systems.
2018
Frequency estimation; phase measurement; phasor measurement units (PMUs); rate of change of frequency (ROCOF); unbalanced three-phase electric systems; voltage measurement; Instrumentation; Electrical and Electronic Engineering
File in questo prodotto:
File Dimensione Formato  
08253484_editorial.pdf

Solo gestori archivio

Descrizione: versione editoriale
Tipologia: versione editoriale
Dimensione 1.7 MB
Formato Adobe PDF
1.7 MB Adobe PDF   Visualizza/Apri   Richiedi una copia
TIM_unbalance_final_accepted_disclaimer.pdf

accesso aperto

Descrizione: accepted paper to share
Tipologia: versione post-print
Dimensione 857.9 kB
Formato Adobe PDF
857.9 kB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11584/248234
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 24
  • ???jsp.display-item.citation.isi??? 21
social impact